VOC Reduction

Authors
Robin Svedlind and Filip Sandberg
Facility
Camfil Laboratories – Tech Center; Sweden
Download
Full Report

Objective

To evaluate the particulate and molecular efficiency of the Defend 1050 in a test chamber using Toluene.

Methodology

Test method: CADR

Toluene was generated in the laskin nozzle and injected into a room until a pre-set concentration was achieved then the air cleaner was turned on. The results were then compared to the normal reduction of particles over time in the test chamber.

Summary of Results

The Defend 1050 produced a CADR of 351 CFM. It removed 90% of the toluene within 6 minutes on the high speed and 90% within 16 minutes on the low speed.

Contact Us

USA Headquarters
290 Harbor Drive, 2nd Floor, Stamford, CT 06902
1 866 508 1118
info@wellairsolutions.com

Ireland Headquarters
DCU Innovation Campus
Old Finglas Road
Glasnevin, Dublin D11 KXN4
+353 1 907 2750
info@wellairsolutions.com

Social

Partners

q